Attic Infiltration Calculator

Add-a-hole zone pressure test: how much of a house's blower door leakage runs through the attic.

Test readings

CFM
Normal blower door test
Pa
Pressure between attic and house, house at 50 Pa
CFM
CFM after adding a hole big enough for more than a 6 Pa change
Pa
Pressure between attic and house with the hole open
Flow exponent between the attic and outside

Result

Maximum reduction

– CFM50

CFM50 added by the hole–
Attic to outside, start–
Attic to outside, end–
Pressure change–
Attic-to-outside pressure grew by–
Multiplier–

Reading check

–

If one pressure reading is off by 1 Pa, the answer lands between –

Ne is the flow exponent between the zone and the outside. From the guy who developed the math:

"The 0.60 might be a better estimate if the zone is an attic, but it can be argued either way." Michael Blasnik

Reading check: the calculator reruns the formula with each pressure reading moved up and down 1 Pa and shows the lowest and highest answers. Steady means the answer moves 15% or less, Touchy up to 30%, Unreliable more than 30%. The answer is steadiest when the hole makes the attic-to-outside pressure at least double.

Formula, same as the original page:
multiplier = (50 − start Pa)^Ne ÷ ((50 − end Pa)^Ne − (50 − start Pa)^Ne)
maximum reduction = (end CFM50 − start CFM50) × multiplier, rounded up.