Attic Infiltration Calculator
Add-a-hole zone pressure test: how much of a house's blower door leakage runs through the attic.
Test readings
Result
Maximum reduction
– CFM50
| CFM50 added by the hole | – |
| Attic to outside, start | – |
| Attic to outside, end | – |
| Pressure change | – |
| Attic-to-outside pressure grew by | – |
| Multiplier | – |
Reading check
–If one pressure reading is off by 1 Pa, the answer lands between –
Ne is the flow exponent between the zone and the outside. From the guy who developed the math:
"The 0.60 might be a better estimate if the zone is an attic, but it can be argued either way." Michael Blasnik
Reading check: the calculator reruns the formula with each pressure reading moved up and down 1 Pa and shows the lowest and highest answers. Steady means the answer moves 15% or less, Touchy up to 30%, Unreliable more than 30%. The answer is steadiest when the hole makes the attic-to-outside pressure at least double.
Formula, same as the original page:
multiplier = (50 − start Pa)^Ne ÷ ((50 − end Pa)^Ne − (50 − start Pa)^Ne)
maximum reduction = (end CFM50 − start CFM50) × multiplier, rounded up.